Thermal Imaging Inspection Report

Thermal Report on the Electrical Facilities at:

[Enter Full Address of Inspection Site]

Report To:

[Enter Client Name]

Date of Inspection:

[DD-MM-YYYY]

Thermographer:

[Enter Inspector's Name]

[Enter License No.]

Generated by: [Enter Your Company Name]

[Your Company Address] | [Your Company Phone | Email | Website]

1. Introduction

This section outlines the scope and limitations of the thermal inspection.

  • Plant Inspected: A comprehensive thermal inspection was performed on the electrical switchboards and associated components listed within this report.
  • Limitations: The infrared camera measures surface temperature only and cannot detect issues behind sealed metal, glass, or plastic covers. Panels were only removed where it was safe to do so without disrupting power. This report represents a "snapshot in time" of the system's condition under the load present during the inspection.
  • The Report: This is a "report by exception," meaning it primarily details thermal abnormalities. A selection of images showing equipment in good condition may be included for reference. Findings are prioritized based on the urgency of the required response (see "General Notes" at the end of this report).
  • Follow-Up: We recommend continued thermal inspections at regular twelve (12) monthly intervals to assist with preventative maintenance, reduce the risk of unscheduled downtime, and comply with insurance requirements.

3. Inspection Findings

This section presents the thermal and digital images for each component inspected, along with observations and key data.

3.1 Component: [e.g., Main Switchboard - Fuses & Terminations]

THERMAL IMAGE

Thermal Image

DIGITAL IMAGE

Digital Photo

Inspection Details:

  • Client: [Enter Client Name]
  • Location: [Enter Full Address of Inspection Site]
  • Equipment: [e.g., Main Switchboard (MSB)]
  • Observation: [e.g., "No thermal abnormality exists. The image is to show the general condition of the equipment."]
  • Priority: [Enter Priority Rating, e.g., 4]

Temperature Data:

  • Max Temperature: [-- °C]
  • Average Temperature: [-- °C]
  • Min Temperature: [-- °C]

5. General Notes & Basis of Priorities

The recommendations given are based on observations at the time of inspection. Repairs should only be undertaken after a full assessment by the owner and/or a qualified repairer.

Priority Temperature Difference Fault Temp. Suggested Action
1 > 30°C > 100°C A serious abnormality is present. Immediate repair is recommended.
2 20°C - 30°C 75°C - 100°C Abnormality found. Repair as soon as possible.
3 10°C - 20°C 50°C - 75°C Abnormality noted. Should be checked and rectified when convenient.
4 No abnormality -- Image shows the general condition of equipment. No action required.